ASS RCD does not trip

If you touch a live part and get an electric...

iFixit Library ASS FI Schutzschalter Moderate 30 minutes Guide 160367
Open the authorised source
Licensed iFixit integration

This attributed iFixit guide is displayed through Fixonic's recorded commercial API permission. iFixit remains the independent source and author of the procedure.

Guide overview

Before you begin

If you touch a live part and get an electric shock, the residual current device (RCD) detects it and switches off in a flash. Having such a safety switch on your cable makes you feel safe (and rightly so), whether you're working on electronics or trimming your hedge. It's just a problem if the protection fails at the critical moment......

Step 1

unscrewing

  • the circuit breaker works with the IC RV4145, which requires 26V, but there are 230V on the line, the excess is 'burned off' in a large resistor
  • directly next to the resistor sits (stands) a small electrolytic capacitor, a design flaw, because electrolytic capacitors do not like heat ..... after a few years they are defective
  • and the dangerous thing here is, you don't notice anything ..... current still flows .......
  • Only by pressing the 'Test' button do you notice the defect!
Step 2

Replace electrolytic capacitor

  • Desolder the defective electrolytic capacitor.
  • To make the new electrolytic capacitor last longer, install it on the underside... it is not as hot there.
  • Observe the polarity, see the photo for +.
  • When testing without switching off, the small test resistance can burn out and must then also be replaced; 6.8 kΩ for 30mA RCD (18 kΩ in the photo).
Step 3

testing !

  • so, attention, such an RCD is not 'fail-safe'
  • therefore regularly press the 'Test' button !