Nordgas Atlantis 25 hww Heating Repair (error code E 18)

In the Nordgas Atlantis 25 HWW, the error code...

iFixit Library Nordgas Atlantis 25 hww Moderate 10 hours Guide 179042
Open the authorised source
Licensed iFixit integration

This attributed iFixit guide is displayed through Fixonic's recorded commercial API permission. iFixit remains the independent source and author of the procedure.

Guide overview

Before you begin

In the Nordgas Atlantis 25 HWW, the error code E18 indicates insufficient circulation. The attached manufacturer manual cites a clogged heat exchanger or a damaged or dirty circulation pump as possible causes. Check the cause before you open the pump. I needed about ten hours for the repair, including troubleshooting. Observe the safety and qualification requirements in the manufacturer manual for work on the electrical system.

Step 1

Prepare the device and open the casing

  • Turn off the boiler, disconnect its power supply, and let the heating water cool down. Observe the safety and qualification instructions in the provided manufacturer's manual. Work on the gas path is not covered in this guide.
  • Release the two screws at the front bottom and tilt the cover away carefully.
Step 2

Preparing the heating circuit

  • Shut off the supply and return lines and drain the water from the affected device area. Only open the pump once the heating circuit is depressurized and cooled down.
  • Observe the instructions on page 31 of the attached manual for subsequent refilling and venting.
Step 3

Remove the pump head

  • Löse bei sicher vorbereitetem, drucklosem Gerät die vier Befestigungsschrauben des Pumpenkopfs und trenne ihn vorsichtig vom Pumpengehäuse.
  • Point 1 in the second image is the pump bleeder screw.
Step 4

Pump inspection and refilling

  • I pulled out the impeller with the bearing housing and tapped it back in by about 4 mm with a hammer.
  • Only change the position of the impeller according to the specifications for your pump type. Do not adopt the 4 mm shift as a general adjustment measurement.
  • Check the original position and tightness of all loosened connections before reassembly.
  • For refilling, page 31 of the manual describes a cold system pressure of 1.2 bar: fill via the valve R indicated there, close the valve, bleed the radiators, and top up to 1.2 bar if necessary.
  • Observe the valve positions and venting instructions in the manual when refilling. Check for leaks before putting the boiler back into operation.