How to clean the Vent-Axia MVHR Cell

This guide will show you how to clean the heat...

iFixit Library Vent-Axia MVHR Moderate 40 minutes Guide 24911
Open the authorised source
Licensed iFixit integration

This attributed iFixit guide is displayed through Fixonic's recorded commercial API permission. iFixit remains the independent source and author of the procedure.

Guide overview

Before you begin

This guide will show you how to clean the heat exchange cell which Vent-Axia advise should be done once a year. Remember apart from when you clean the heat exchange cell it should never be turned off.

Step 1

Repair step

  • Turn the heat recovery system off at the wall.
Step 2

Repair step

  • Remove the 6 screws from the heat recovery panel.
  • You may need a friend to help you lift the panel off and hold the screws for you!
Step 3

Repair step

  • Remove the internal filter on the left hand side using the pull tab
  • Repeat for the external filter on the right hand side of the cell.
  • If required clean them using a hoover.
  • Do not wash in water under any circumstances
Step 4

Repair step

  • Gently take the cell by the pull tab
  • You may have to rock it gently to get it out.
  • Gently and slowly is the most important step here.
  • The cell will begin to slide out
Step 5

Repair step

  • Clean the cell on each side with a hoover to remove any dust
Step 6

Repair step

  • Fill a bath with warm water and add a small bit of fairy liquid or similar.
  • Place the cell into the water
  • Gently hold the cell
  • Rock the cell from side to side. Ensure the cell is not scraping the bottom
  • Lift the cell up and let the water drain out.
  • Repeat for each side of the hexagon
  • Remove from the bath and leave to dry
  • Vent Axia tehnical support told me the cell can be a little damp but ensure all water is out the cell.
Step 7

Repair step

  • Clean inside the heat recovery system with the hoover
  • Remove any dead flies
  • Check the fans for any build up of dust
  • If you have the summer bypass fitted (the white grill) Don't yank it, as its attached via a cable.
  • Gently lift it to clean the fan behind
Step 8

Repair step

  • Begin to insert the cell back in.
  • Slide using the plastic tab
  • Ensure the two black arrows meet
Step 9

Repair step

  • Put the cover back on
  • Insert the screws and secure the cover to the MVHR.
  • Leave the internal and external filter out for now
  • We will slide them through the filter flaps later.
Step 10

Repair step

  • Insert the filters into each flap (clean if needed using a hoover)
  • Close the flap
Step 11

Repair step

  • Turn the heat recovery back on
  • It will go through its initial power on so don't expect the fans to start immediently.
  • If you have a message on the screen saying check filters you can clear it (once the filters have been cleaned) by:
  • Waiting until Normal airflow xx% is displayed on the screen
  • Press and hold the up and down arrows for 5 seconds
  • This will reset the cycle for the filter clean. Whenever you see the check filter message clean the filter (remember this is separate to the cell).
  • Keeping your MVHR cleaned to the Vent-Axia recommendations gives you the best chance of having many years of trouble free service.